ET 200SP DI vs DQ: 6ES7131 vs 6ES7132 Compared
Two ET 200SP modules, same 15 mm housing, same 8 channels — and one digit in the order number decides whether you read a sensor or drive a valve. Here is the three-minute check before you buy.
Photo by Homa Appliances on Unsplash
6ES7131-6BF01-0BA0 is an 8-channel digital input module — it reads 24 V DC signals from sensors. 6ES7132-6BF01-0BA0 is an 8-channel digital output module — it drives loads at 0.5 A per channel. One digit in the order number (131 vs 132) separates them, and the two modules look almost identical on the rail.
A station faults on a night shift, someone reads the failed card off a phone photo, and the replacement arrives as an output module where an input should be. Same 15 mm housing, same eight LEDs, same BaseUnit. Here is the check that prevents a second outage.
Key takeaways
- 131 = DI reads field signals; 132 = DQ drives 24 V loads. They are not interchangeable.
- Both are 8 channels, 15 × 73 × 58 mm, and need a BU type A0 BaseUnit — colour codes CC01 vs CC02.
- The BaseUnit and the 24 V feed are ordered separately; the server module comes with the interface module.
- Siemens lists the older -6BF00- DI as discontinued since 01.10.2021, with -6BF01- as successor.
Read the order number, not the housing
Both MLFBs decode the same way: 6ES7 13x is the ET 200SP digital family, 6BF01 the 8-channel standard revision, 0BA0 the packing variant. One character decides everything — 1 for input, 2 for output. The DI is a sinking input (IEC 61131 type 3); the DQ is a PNP sourcing output (DI manual) (DQ manual).
| Dimension | DI 8x24VDC ST 6ES7131-6BF01-0BA0 |
DQ 8x24VDC/0.5A ST 6ES7132-6BF01-0BA0 |
|---|---|---|
| Job | Reads 8 sensor / switch signals | Drives 8 valves, lamps, relay coils |
| Electrical | 24 V DC sinking inputs, type 3, 2.5 mA typ. | 24 V DC PNP outputs, 0.5 A per channel, 4 A per module |
| Timing | Input delay 0.05–20 ms, parameterisable | 50 µs on / 100 µs off; 100 Hz max on resistive load |
| Diagnostics | Sensor-supply short circuit, wire break, supply voltage | Short circuit to L+/M, wire break, substitute values |
| Listed price* | From $43.05 | From $40.36 |
| Pros / cons | Clear sensor diagnostics; drives nothing | Drives loads directly; cannot read a signal |
* Prices are chipsgate.com listed prices captured 14 November 2026; surplus stock and condition change.
In our most recent conveyor-station swap
A failed channel on a remote ET 200SP station turned into a same-day parts run. Three checks kept it to one visit:
- Photograph the MLFB. Field wiring says nothing about direction; the printed order number does.
- Open the TIA Portal project. The hardware configuration names the module in its slot. Siemens lists the older -6BF00- DI as PM500 discontinued since 1 October 2021, with -6BF01- as successor (Siemens Industry Mall), so an old project needs a compatibility check.
- Order the BaseUnit too. We keep 6ES7193-6BP00-0DA0 (BU15-P16+A0+2D) in stock for exactly this reason.
Pro tip: light BaseUnits open a new potential group and need their own fused 24 V feed; dark ones continue the group from the left. The server module terminating the backplane bus already ships with the IM 155-6 interface module — do not order it separately.
Which one belongs on your order
If the wire brings a signal in, buy the DI 8x24VDC ST; if it takes 24 V out to a load, buy the DQ 8x24VDC/0.5A ST. Add a BU type A0 BaseUnit for each module. Both are active product lines, so on the surplus market condition and lead time vary, not the specification.
Check current stock and condition for Siemens ET 200SP modules — send us the MLFB and a nameplate photo and we will confirm the cross before shipping.
FAQ
Can I fit a DQ module where a DI module failed?
No — signal direction is reversed. A DQ sources 24 V to a load; a DI only senses it. The slot accepts the card physically, but the station will not behave as configured.
Do I need to order a BaseUnit as well?
Yes — both modules ship as electronics only. The BU type A0 BaseUnit, 24 V feed and terminals are separate line items; a bare module cannot be wired.
Will a -6BF01- replace a -6BF00- in an existing project?
It depends on the engineering version. Siemens names -6BF01- as successor, but hardware functional state and GSD/TIA Portal support differ — check the project before swapping a running station.